WASHINGTON, Oct. 21 -- The Nuclear Regulatory Commission issued the following event notification (No. 54339) involving the Arkansas Nuclear power reactor in Arkansas:
CONTROL ROOM ENVELOPE BREACH
"At 1030 CDT, it was discovered that the loop seal on the condensate drain was empty for VUC-9 Control Room AC Unit. This creates a breach in the Control Room envelope. Unit 2 entered [Technical Specification] T.S. 3.7.6.1 Action D. Unit 1 is in Mode 6; therefore, not in a . . .
CONTROL ROOM ENVELOPE BREACH